For linear inputs, the span will be checked at the end of
configurationprocedure. If it will be wrong, error code "E204"
will be displayed. To end the configuration procedure correct
the wrong value.
P 5
P 5
P 5
P 5
P 5
Offset
Offset
adjustment
adjustment
Offset
Offset
Offset
adjustment
adjustment
adjustment
Range: from -500 to 500 units.
N O T E S
N O T E S
N O T E S
N O T E S
N O T E S :
a) The decimal point will be automatically positioned as selected
for the main input P2.
b) The offset value will be algebraically added to the measured
value.
.
Read-out
Real curve
P5
Adjusted curve
Input
P 6
P 6
P 6
P 6
P 6
Function of output 1 (main)
Function of output 1 (main)
Function of output 1 (main)
Function of output 1 (main)
Function of output 1 (main)
Range:
dir
= Time proportioning control output with
direct action (Cooling)
rEV
= Time proportioning control output with
reverse action (Heating)
ALr.1
= Output for alarm 1
REVERSE ACTION
DIRECT ACTION
Input
Input
t
Output
Output
t
fks-MK1-1-A0.pmd
8
N O T E S
N O T E S :
N O T E S
N O T E S
N O T E S
a) If "rEV" has been selected and "P10" (function of output 2)
is different from "CooL":
1 "P53", if less than zero, is forced to zero.
2 "OLH", if less than or equal to zero, is forced to 100.
3 "OLL", if less than zero, is forced to zero.
4 "IP" is forced to 50.
b) If "dir" has been selected:
1 "P10", if equal to "CooL", is forced to "nonE"
2 "P53", if less than zero, is forced to zero.
3 "OLH", if less than or equal to zero, is forced to 100.
4 "OLL", if less than zero, is forced to zero.
5 "IP" is forced to 50.
c) If the output for alarm 1 ("ALr.1") has been selected:
1 "P10", if set to "bAnd","dEV" or "CooL", is forced to
"nonE"
2 "P56" is forced to "nonE"
3 The threshold of "AL.1" is checked and, if out of range,
aligned to "P3".
NOTE: setting "P6" as alarm output, the instrument
becomes an indicator and all the configuration and
operative parameters (e.g. SP, PB, TI, etc.) related
with PID control will be skipped.
P 7
P 7
P 7
P 7
P 7
Alarm 1: operating mode
Alarm 1: operating mode
Alarm 1: operating mode
Alarm 1: operating mode
Alarm 1: operating mode
This parameter is only available if output 1 is configured as
alarm 1 ("P6" = "ALr.1")
Range:
H.A.
= High alarm with automatic reset
L.A.
= Low alarm with automatic reset
H.L.
= High alarm with manual reset (latched
alarm)
L.L.
= Low alarm with manual reset (latched
t
alarm)
t
GB
8