Software key
Software key
Software key
Software key
Software key
This parameter is available if "P18" is equal to or greater than 2
(see sect. 5.2).
Range:
from 2 to 9999. Enter the code assigned and press
FUNC
FUNC
the FUNC
FUNC
FUNC key.
N O T E :
N O T E :
N O T E :
N O T E :
N O T E :
- At first the parameter protection state will appear on the
display.
On
Protection activated
OFF
Protection deactivated
Set the value assigned to "P18" to deactivate the protection,
set a different value to activate it.
A L . 1
A L . 1
A L . 1
A L . 1
A L . 1
Threshold alarm
Threshold alarm 1 1 1 1 1
Threshold alarm
Threshold alarm
Threshold alarm
This parameter is only available if output 1 is configured as alarm
("P6" = "ALr.1", see section 5.2).
Range:
- from "P3" to "P4".
H S A . 1
H S A . 1
H S A . 1
H S A . 1
H S A . 1
Hysteresis alarm 1
Hysteresis alarm 1
Hysteresis alarm 1
Hysteresis alarm 1
Hysteresis alarm 1
This parameter is only available if output 1 is configured as alarm
("P6" = "ALr.1", see section 5.2).
Range: from 1 to 200 digits
fks-MK1-1-A0.pmd
14
A L . 2
A L . 2
A L . 2
A L . 2
A L . 2
Threshold alarm
Threshold alarm
Threshold alarm 2 2 2 2 2
Threshold alarm
Threshold alarm
This parameter is only available if output 2 is configured as alarm
("P10" = "Proc", "bAnd" or "dEV", see section 5.2).
Range:
- from "P3" to "P4" if process alarm ("Proc")
- from 0 to 1000 if range alarm ("bAnd")
- from -1000 to 1000 if deviation alarm ("dEV")
H S A . 2
H S A . 2
H S A . 2
H S A . 2
H S A . 2
Hysteresis alarm 2
Hysteresis alarm 2
Hysteresis alarm 2
Hysteresis alarm 2
Hysteresis alarm 2
This parameter is only available if output 2 is configured as alarm
("P10" = "Proc", "bAnd" or "dEV", see section 5.2).
Range: from 1 to 200 units
N O T E :
N O T E :
N O T E :
N O T E :
N O T E :
- If "P10" is programmed as band alarm, the hysteresis is
limited by the threshold value set in the previous point.
P B
P B
P B
P B
P B
Proportional range
Proportional range
Proportional range
Proportional range
Proportional range
This parameter is available when at least one control output is
configured.
Range: from 1.0% to 100.0% of the input span ("P4" - "P3).
Set 0.0% for On/OFF control action
N O T E S
N O T E S :
N O T E S
N O T E S
N O T E S
a) The Pb resolution will be equal to 0.1% up to 10.0% and 1%
from 10.0% up to 100.0%.
b) When the instrument uses the SMART algorithm, the value of
"Pb" will be limited as selected by parameters "P62" and
"P63" (see "Advanced configuration parameters").