Connecting The Bus Coupler As An Intermediate Station - Aventics HF03 LG Mode D'emploi

Masquer les pouces Voir aussi pour HF03 LG:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 87
BUS IN
X71
1
1
2
2
5
5
3
3
4
4
BUS OUT
X72
1
2
5
4 3
1
X71
X72
2
X10
AVENTICS | EtherCAT | R412012792–BDL–001–AB
Table 5:
Assignment X71 (BUS IN) and X72
(BUS OUT), M12, D-coded
Pin
Signal
Meaning
1
TD+
Transmit pos.
2
RD+
Receive pos.
3
TD–
Transmit neg.
4
RD–
Receive neg.
5
Housing
Shield or functional grounding
X71/X72: communication connection
The connection technology and plug assignment
comply with the specifications in the technical
directives.
6.3.2 Connecting the bus coupler as an
intermediate station
1. Set up the correct pin assignment (see Tab. 5 on
page 61) on the plug connections if you do not use
pre-assembled cables.
2. Connect the incoming bus connection to the X71
(BUS IN) plug (1).
3. Connect the outgoing bus connection to the X72
(BUS OUT) plug (2).
The EtherCAT cable must at least fulfil the
requirements for category CAT5e and should be a
cable with double shielding (S/STP) with a maximum
length of 100 m.
4. Connect the shield on both sides of the bus cable
directly to the plug housing (EMC housing) if non-pre-
assembled cables and plugs with metal housing are
used. This protects data lines from terminal
interference.
Ensure that the plug housing is securely fitted to the
bus coupler housing.
61
Assembly

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Hf04 d-sub

Table des Matières