Function
X1.2/K11
Relay output normally−closed
contact
X1.2/K12
Mid position contact
X1.2/K14
Relay output − normally−open
contact
PES
HF−shield end by PE connection through shield bracket.
)
Note!
For switching the control signals use shielded cables and establish an HF
l
shield termination by PE connection.
For mains potential switching unshielded cables are sufficient.
l
With inductive or capacitive loads a corresponding protective circuit is
l
required in order to protect the relay contacts!
The service life of the relay depends on the type of load (ohmic, inductive or
l
capacitive) and the value of the switching capacity.
The output message can be changed under C0008 or C0415/1.
l
L
Message
Relay position set
(Lenze setting)
open
closed
EDK82EV222 DE/EN/FR 10.1
Electrical installation

Connection of relay output

Technical data
TRIP
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.16 A
TRIP
5
−24−8200vec013