3
Electrical installation
Mains connection 400 V/500 V
Fuses and cable cross−sections (operation with rated power)
8200 vector
Type
[kW]
E82EV551K4C
0.55
E82EV751K4C
0.75
E82EV152K4C
1.5
E82EV222K4C
2.2
8200 vector
Type
[kW]
E82EV551K4C
0.55
E82EV751K4C
0.75
E82EV152K4C
1.5
E82EV222K4C
2.2

Fuse
E.l.c.b.
1)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: Voltage 500 ... 600 V, tripping characteristic "H", "K5" or "CC"
2)
All−current sensitive e.l.c.b. for the use with E82EVxxxK4C0xx
3)
All−current sensitive e.l.c.b. for the use with E82EVxxxK4C2xx
Observe national and regional regulations (e. g. VDE 0113, EN 60204)
102
Installation to EN 60204−1

mains
M6 A
3/PE AC
M6 A
320 ... 550 V;
M10 A
45 ... 65 Hz
M10 A
Installation to EN 60204−1

mains
M6 A
3/PE AC
M6 A
320 ... 550 V;
M10 A
45 ... 65 Hz
M10 A
EDK82EV222 DE/EN/FR 10.1
Operation without mains choke
Installation to UL

L1, L2, L3,
PE
2
[mm
]
B6 A
1
5 A
B6 A
1
5 A
B10 A
1.5
10 A
B10 A
1.5
10 A
Operating with mains choke
Installation to UL

L1, L2, L3,
PE
2
[mm
]
B6 A
1
5 A
B6 A
1
5 A
B10 A
1.5
10 A
B10 A
1.5
10 A
1)
L1, L2, L3,
FI
PE
[AWG]
18
³ 300 mA
18
2)
³ 30 mA
3)
16
16
1)
L1, L2, L3,
FI
PE
[AWG]
18
³ 300 mA
18
2)
³ 30 mA
3)
16
16
L