Commissioning
Using the keypad E82ZBC − Linear V/f characteristic control
The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.
Switch−on sequence
1.
Attach the keypad
2.
Ensure that controller inhibit is active after
mains connection.
3.
Switch on the mains
4.
The keypad is in Disp" mode after approx. 2 s
and indicates the output frequency (C0050)
f
5.
Change to the
basic settings for your drive
6.
Adapt the voltage range/current range to the
analog setpoint (C0034)
Lenze setting: −0−,
(0 ... 5 V/0 ... 10 V/0 ... 20 mA)
7.
Adapt the terminal configuration to the wiring
(C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpoint selection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW operation
8.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
9.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
120
mode to configure the
X3
20
28
ON
Œ
PS
0050
000
000
Hi
Hz
Lo
Œ
0050
000
Hi
Lo
Œ
0034
Hi
Lo
Œ
0007
Hi
Lo
[f]
C0011
C0010
0 %
100 %
EDK82EV222 DE/EN/FR 10.1
Note
Terminal X3/28 = LOW
misc001
misc002
The menu
is active
USEr
1
Blinking on the display:
1
PS
000
Hz
Set the DIP switch on the
1
PS
000
standard I/O to the same range (see
0
Mounting Instructions for the
standard I/O)
1
PS
000
0
0050
L

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Edk82ev222

Table des Matières