7
Commissioning
The most important codes for commissioning
Code
No.
Name
C0002*
Parameter set
s
management
−31−
uSEr
Restorage of
default setting
C0002*
Parameter set
s
transfer using
the keypad
uSEr
(cont.)
138
Possible settings
Lenze Selection
0
0
Ready
1
Lenze setting
2
Lenze setting
3
Lenze setting
4
Lenze setting
31
Lenze setting
61
Lenze setting
62
Lenze setting
63
Lenze setting
64
Lenze setting
ð
Keypad
70
With function module Application−I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet/CANopen
10
With all other function modules
ð
PAR1
ð
PAR2
ð
PAR3
ð
PAR4
ð
FPAR1
ð
PAR1 + FPAR1
ð
PAR2 + FPAR1
ð
PAR3 + FPAR1
ð
PAR4 + FPAR1
Controller
EDK82EV222 DE/EN/FR 10.1
IMPORTANT
PAR1 ... PAR4:
l
Parameter sets of the controller
PAR1 ... PAR4 also contain
l
parameters for Standard−I/O,
Application−I/O, AS interface or
system bus (CAN)
FPAR1:
l
Module−specific parameter set of
the fieldbus function modules
INTERBUS, PROFIBUS−DP,
LECOM−B, DeviceNet/CANopen
FPAR1 is saved in the function
l
module
Restorage of default setting in the
selected parameter set
Restorage of default setting in the
fieldbus function module
Restorage of default setting in the
selected parameter set of the
controller and the fieldbus function
module
Use the keypad to transfer parameter
sets to other controllers.
During transfer the parameters
cannot be accessed via other
channels!
All available parameter sets (PAR1 ...
PAR4, and FPAR1) are overwritten with
the corresponding keypad data