Switch−on sequence
14.
Start the motor paramter identification (C0148)
A
Ensure that the controller is inhibited
B
Set C0148 = 1
C
Enable the controller.
D
If the segment becomes active after approx.
c
30 s,
inhibit the controller once again.
15.
Activate the motor temperature monitoring
(C0119), if a PTC or thermal contact is
connected to the terminal X2.2
Lenze setting: switched−off
16.
Setpoint selection
17.
Enable the controller.
18.
The drive should be running now
)
Note!
In the menu "Diagnostic" the most important drive parameters can be
monitored
L
Using the keypad XT EMZ9371BC − Vector control
TV
e. g. via potentiometer at the
terminals 7, 8, 9
EDK82EV222 DE/EN/FR 10.1
Commissioning
Note
Only when the motor is cold!
X3
Terminal X3/28 = LOW
20
28
misc001
press
X3
l
20
28
misc002
l
X3
l
20
28
l
misc001
l
l
Setting possibilities: (^ 145)
X3
Terminal X3/28 = HIGH
20
28
misc002
CW rotation: X3/E4 = LOW
CCW rotation: X3/E4 = HIGH
If the drive does not start, press
U
7
Terminal X3/28 = HIGH
The identification starts:
c
– The segment
Off
– The motor makes a
high−pitched tone. The motor
does not rotate!
Terminal X3/28 = LOW
Identification is completed.
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance
(C0092)
Measured and stored:
– Motor stator resistance
(C0084) = Total resistance of
motor cable and motor
135