Electrical installation

Connection of motor / brake resistor

PES
PE
Use low−capacity motor cables! (core/core up to 1.5 mm
The shorter the motor cables, the better the drive response!
PES
HF−shield end by PE connection through shield bracket or EMC cable connection.
X2.1/PE
Earthing of the 8200 vector at the output side
X2.1/BR1,
Connection terminals for the brake resistor
X2.1/BR2
(For information about the operation with brake resistor see the Operating Instructions)
X2.2/T1, X2.2/T2
Connection terminals motor temperature monitoring through PTC thermistors or thermal contacts
Activate motor temperature monitoring under C0119 (e. g. C0119 = 1)!
Cable cross−sections U, V, W, PE
Type
E82EV251K2C / E82EV371K2C
E82EV551K2C / E82EV751K2C
E82EV152K2C / E82EV222K2C
{
Danger!
After the connection of a PTC thermistor or thermal contact all control
l
terminals only have a basic insulation (single insulating distance).
Protection against contact in the event of a defective insulating distance
l
can only be ensured by external measures (e.g. double insulation).
104
8200 vector
X2.2
T1 T2
PE
W V U
PES
PE
PES
PE
3~
PTC
PE
3~
£ 75 pF/m; from 2.5 mm
2
2
mm
AWG
Type
1
18
1
18
E82EV551K4C / E82EV751K4C
1.5
16
E82EV152K4C / E82EV222K4C
EDK82EV222 DE/EN/FR 10.1
X2.1
BR2 BR1
PES
PES
PES
X2.2
ϑ>
PES
M
PES
M
£ 100 pF/m; core/shield £ 150 pF/m)
2
X2.1
−23−8200vec009
2
mm
AWG
1
18
1.5
16
L