Connection Of Motor / Brake Resistor - Lenze 8200 vector Instructions De Montage

Masquer les pouces Voir aussi pour 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Show/Hide Bookmarks
Electrical installation
4

Connection of motor / brake resistor

Abb. 1-11
Use low-capacity motor cables! (Core/core ≤ 75 pF/m, core/shield ≤ 150 pF/m)
The shorter the motor cables, the better the drive response!
PES
HF-screen end by PE connection through screen clamp or EMC cable connection.
X2.1/PE
Earthing of the 8200 vector at the output side
X2.1/BR1,
Connection terminals for the brake resistor
X2.1/BR2
(For information about the operation with brake resistor see the Operating Instructions)
X2.2/T1,
Connection terminals motor temperature monitoring through PTC thermistors or thermal
X2.2/T2
contacts
Activate motor temperature monitoring under C0119 (e. g. C0119 = 1)!
Cable cross-sections U, V, W, PE
Type
E82EV251K2B / E82EV371K2B
E82EV551K2B / E82EV751K2B
E82EV152K2B / E82EV222K2B
Danger!
After the connection of a PTC thermistor or thermal contact all control terminals
l
only have a basic insulation (single isolating distance).
Protection against contact in the event of a defective insulating distance can only be
l
ensured by external measures (e.g. double insulation).
18
8200 vector
X2.2
T1 T2
X2.1
PE
W V U
PES
PE
PES
J>
M
PE
3~
PTC
M
PE
3~
2
mm
AWG
1
18
1
18
1.5
16
EDK82EV222 DE/EN/FR 6.0
BR2 BR1
PES
PES
PES
X2.2
X2.1
PES
PES
Type
E82EV551K4B / E82EV751K4B
E82EV152K4B / E82EV222K4B
8200vec009
2
mm
AWG
1
18
1.5
16
L