Electrical installation

Connection of motor / brake resistor

T1 T2
X2.2
PES
Abb. 1-11
PES
Use low-capacity motor cables! (Core/core ≤ 75 pF/m, core/shield ≤ 150 pF/m)
The shorter the motor cables, the better the drive response!
PES
HF-screen end by PE connection through screen bracket. or EMC cable connection.
X2.1/PE
Earthing of the 8200 vector at the output side
X2.1/BR1,
Connection terminals for the brake resistor
X2.1/BR2
(For information about the operation with brake resistor see the Operating Instructions)
X2.2/T1,
Connection terminals motor temperature monitoring through PTC thermistors or thermal
X2.2/T2
contacts
Activate motor temperature monitoring under C0119 (e. g. C0119 = 1)!
Cable cross-sections U, V, W, PE
Type
mm
E82EV302K2B
2.5
E82EV402K2B
4
E82EV552K2B
6
E82EV752K2B
6
Danger!
After the connection of a PTC thermistor or thermal contact all control terminals
l
only have a basic insulation (single insulating distance).
l
Protection against contact in the event of a defective insulating distance can only be
ensured by external measures (e.g. double insulation).
14
8200 vector
U
X2.1
V W
BR1
BR2
PES
PES
PES
PE
ϑ>
PES
PE
M
3~
PTC
PES
M
PE
3~
2
AWG
12
10
10
10
EDK82EV3 DE/EN/FR 2.0
0,7...0,8 Nm
6.2...7.1 lb-in
6 mm / 0.24 in
PE
X2.2
Type
E82EV302K4B
E82EV402K4B
E82EV552K4B
E82EV752K4B
E82EV113K4B
X2.1
8200vec064
2
mm
AWG
1
16
1.5
14
2.5
12
4
10
4
10
L