Fault detection and elimination

Fault of the drive

Fault
Cause
Motor does not
DC-bus voltage too low
rotate
(Red LED is blinking every 0.4 s;
keypad display
Controller inhibited
(Green LED is blinking, keypad display:
Automatic start inhibited (C0142 = 0 or 2)
DC injection brake active (DCB)
Mechanical motor brake is not released
Quick stop (QSP) active (keypad display:
Setpoint = 0
JOG setpoint activated and JOG frequency = 0
Active fault
Wrong parameter set active
Control mode C0014 = -4-, -5-, but no motor
parameter identification
Under C0410 several functions, which exclude
each other, are assigned to the same signal
source.
Use internal voltage source X3/20 for function
modules Standard-I/O, INTERBUS, PROFIBUS-DP
or LECOM-B (RS485):
Bridge between X3/7 and X3/39 is missing
Motor does not
Motor does not
Defective motor cable
rotate smoothly
rotate smoothly
Maximum current set too low (C0022, C0023)
Motor underexcited or overexcited
C0084, C0087, C0088, C0089, C0090, C0091
and/or C0092 are not adapted to the motor data
Current
Current
Setting of C0016 too high
consumption of
consumption of
Setting of C0015 too low
motor too high
t
t
hi h
C0084, C0087, C0088, C0089, C0090, C0091
and/or C0092 are not adapted to the motor data
Motor rotates,
With the function
setpoints are "0"
has been selected.
Motor parameter
Motor phase failure detection active (C0597 = 1) Deactivate with C0597 = 0 before
identification
stops with error
stops with error
LP1
LP1
Motor too small compared with rated power
DC injection brake is active (terminal assigned)
Unacceptable
various
drive response
with vector
control
40
L L L L U U U U
)
c
j
of the keypad a setpoint
EDK82EV3 DE/EN/FR 2.0
Remedy
Check mains voltage
Remove the controller inhibit,
controller inhibit can be set through
)
several sources
LOW-HIGH signal at X3/28
If necessary, correct start condition
(C0142)
Deactivate DC-injection brake
Manual or electrical release of
mechanical motor brake
c
Remove quick stop
)
Setpoint selection
JOG setpoint selection (C0037 ...
C0039)
Eliminate fault
Change to correct parameter set via
terminal
Motor parameter identification (C0148)
Correct configuration in C0410
Bridge terminals
Check motor cable
Adaptation to the application
Check parameter setting (C0015,
C0016, C0014)
Manual adaptation or identification of
motor parameters (C0148)
Correct setting
Correct setting
Manual adaptation or identification of
motor parameters (C0148)
Set the setpoint to "0" by C0140 = 0
identification; reactivate after
identification (C0597 = 1)
Vector control optimisation ( ¶ 30)