Troubleshooting and fault elimination
8.1
Troubleshooting
Detecting breakdowns
A breakdown can be detected quickly via the LEDs at the controller or via the status
information at the keypad.
Analysing errors
Analyse the error using the history buffer. The list of fault messages gives you advice how
to remove the fault. (¶ 186)
8.1.1
Status display via controller LEDs
During operation the operating status of the controller is shown by 2 LEDs.
LED red
Off
On
Off
Off
Blinking quickly
Blinking slowly
8.1.2
Fault analysis with the history buffer
Retracing faults
Via the history buffer you can retrace faults. Fault messages are saved in the 4 memory
locations in the order of their occurrence. The memory locations can be called via codes.
Structure of the history buffer
Code
Memory location
C0161 History buffer location 1 Active fault
C0162 History buffer location 2 Last fault
C0163 History buffer location 3 Penultimate fault
C0164 History buffer location 4
EDK82EV903 DE/EN/FR 5.1
Troubleshooting and fault elimination
LED green
Operating status
On
Controller enabled
On
Mains switched on and automatic start inhibited
Blinking slowly
Controller inhibited
Blinking quickly
Motor parameter identification is carried out
Off
Undervoltage or overvoltage
Off
Fault active, check in C0161
Entry
Third from last
fault
l
Troubleshooting
Status display via controller LEDs
Comment
If the fault is no longer pending or has been
acknowledged:
l
The contents of memory locations 1 ... 3 are shifted
one memory location "higher".
l
The contents of memory location 4 are no longer
included in the history buffer and cannot be called
anymore.
l
Memory location 1 is deleted (= no active fault).
8