Lenze 8200 vector Instructions De Montage page 158

Masquer les pouces Voir aussi pour 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5
Electrical installation
Connection of relay output K
Technical data
Terminal
Description
X3.1/K32
Safety relay K
X3.1/K31
1st disconnecting path
X3.1/33
X3.1/34
Terminal data
Cable type
Wiring
}
Danger!
Faulty operation in case of earth faults possible
The correct functioning of the safety function is not ensured if an earth fault
occurs.
Possible consequences:
ƒ
Protective measures:
The electrical reference point for the coil of the safety relay K
connected to the PE conductor system (EN 60204−1, paragraph 9.4.3)!
158
SR
Range
Coil voltage at +20 °C
SR
Coil resistance at +20 °C
Rated coil power
Max. switching voltage
Max. switching capacity, AC
Max. switching current (ohmic load)
Recommended minimum load
Max. operating frequency
Mechanical service life
Electrical service life
at AC 250 V
(ohmic load)
at DC 24 V
(ohmic load)
Wire end ferrule
Directly
coupled
to the
mains
Flexible With plastic sleeve
A failure of the safety function can lead to death, severe injuries or damage
to material.
l
Values
DC 24 V (20 ... 30 V)
823 W ±10 %
Approx. 700 mW
AC 250 V, DC 250 V (0.45 A)
1500 VA
AC 6 A (250 V), DC 6 A (50 V)
> 50 mW
6 switching operations per minute
7
10
5
10
6
10
7
10
6 × 10
6
10
1.5 × 10
7
10
Cable cross−section
Tightening torque Stripping length
2
2.5 mm
(AWG 14)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)
2
2.5 mm
(AWG 14)
switching cycles
switching cycles at 6 A
switching cycles at 1 A
switching cycles at 0.25 A
3
switching cycles at 6 A
switching cycles at 3 A
6
switching cycles at 1 A
switching cycles at 0.1 A
5 mm
must be
SR
EDK82EV903 DE/EN/FR 5.1