Sicherheitshinweise Für Die Installation Nach Ul - Lenze 8200 vector Instructions De Montage

Masquer les pouces Voir aussi pour 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2
Sicherheitshinweise
Sicherheitshinweise für die Installation nach UL
2.5
Sicherheitshinweise für die Installation nach UL
J
Warnings!
ƒ
ƒ
ƒ
ƒ
ƒ
20
Motor Overload Protection
– For information on the protection level of the internal overload protection
for a motor load, see the corresponding manuals or software helps.
– If the integral solid state motor overload protection is not used, external or
remote overload protection must be provided.
Branch Circuit Protection
– The integral solid state protection does not provide branch circuit
protection.
– Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any
additional codes.
Please observe the specifications for fuses and screw−tightening torques in
these instructions.
E82xV153K4B ... E82xV303K4B:
– Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 500 V maximum. When protected by fuses.
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by J, T or R class
fuses
– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.
E82xV453K4B ... E82xV903K4B:
– Suitable for use on a circuit capable of delivering not more than 10000 rms
symmetrical amperes, 500 V maximum. When protected by fuses.
– Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by J, T or R class
fuses
– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.
l
EDK82EV903 DE/EN/FR 5.1

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

E82ev153k4b2E82ev223k4b2E82ev303k4b2

Table des Matières