Resetting fault messages

Eliminating the cause for TRIP error message
After eliminating the cause for a TRIP error message the error message must be reset with
the "TRIP reset" order. Only then the drive will start again.
)
Note!
A TRIP error message can have several causes. The TRIP reset can only be
carried out after all causes for the TRIP have been eliminated.
Manual or automatic TRIP reset
You can select whether errors occurred are to be reset manually or automatically. Mains
disconnection always carries out a TRIP reset independent of the settings under C0170.
)
Note!
If the controller carries out more than eight automatic TRIP resets within ten
minutes, the controller will set TRIP rST (Counter exceeded).
TRIP reset also resets the auto TRIP counter.
Codes for parameter setting
Code
Possible settings
No.
Name
Lenze
C0043*
TRIP reset
v
C0170
Configuration of
v
TRIP reset
C0171
Delay for auto
0.00
TRIP reset
EDK82EV903 DE/EN/FR 5.1
Troubleshooting and fault elimination
Selection
0
No current fault
1
Fault active
TRIP reset by mains switching, s, LOW
0
0
edge at X3/28, via function module or
communication module
1
Like 0 and additionally auto TRIP reset
2
TRIP reset by mains switching, via function
module or communication module
3
TRIP reset by mains switching
0.00
{0.01 s}
l
Resetting fault messages
IMPORTANT
Reset active fault with C0043 = 0
l
TRIP reset via function module or
communication module with
C0043, C0410/12 or C0135 bit 11
l
Auto TRIP reset automatically
resets all faults after the time in
C0171 has elapsed
60.00
8
189