7
Commissioning
Important codes for quick commissioning
Code
Possible settings
No.
Name
Lenze
C0140* Additive
0.00
frequency
setpoint
(NSET1−NADD)
C0148*
Identifying
s
motor data
C0517*
User menu
v
1 Memory 1
2 Memory 2
3 Memory 3
4 Memory 4
5 Memory 5
6 Memory 6
7 Memory 7
8 Memory 8
9 Memory 9
10 Memory 10
182
Selection
−650.00
{0.02 Hz}
0
0
Ready
1
Start identification
l
V/f rated frequency (C0015), slip
compensation (C0021) and motor stator
inductance (C0092) are calculated and
saved
l
The motor stator resistance (C0084) =
total resistance of the motor cable and
motor is measured and saved
50
C0050
Output frequency (MCTRL1−NOUT)
34
C0034
Range of analog setpoint selection
7
C0007
Fixed configuration of digital input signals
10
C0010
Minimum output frequency
11
C0011
Maximum output frequency
12
C0012
Acceleration time main setpoint
13
C0013
Deceleration time main setpoint
15
C0015
V/f rated frequency
16
C0016
V
boost
min
2
C0002
Parameter set transfer
Possible entries for C0517
xxxx
All codes apart from the codes labelled
with "(A)".
l
IMPORTANT
Selection via j function of the
l
650.00
keypad or parameter channel
l
Acts additively on the main
setpoint
l
Value will be stored when
switching the mains or removing
the keypad
l
C0140 is only transferred during
parameter set transfer with GDC
(not with keypad)
Only when the motor is cold!
1. Inhibit controller, wait until drive is
at standstill
2. Enter the correct values from the
motor nameplate in C0087, C0088,
C0089, C0090, C0091
3. Set C0148 = 1, confirm with v
4. Enable controller:
The identification
– starts, c goes out
– the motor "whistles" faintly but
it does not rotate!
– takes approx. 30 s
– is completed when c is lit
again
5. Inhibit controller
After mains switching or in the g
l
function the code from C0517/1 is
displayed.
l
In the Lenze setting the user menu
contains the most important codes
for commissioning the operating
mode "V/f characteristic control
with a linear characteristic"
l
If the password protection is
active, only the codes entered in
C0517 can be freely accessed
l
If less than 10 codes are required,
assign the value "0" (zero) to the
memory locations not used. Please
observe that the software
automatically assigns code C0050
to a memory location that is not
used, if it has not been explicitly
assigned to another memory
location.
Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x = cccc.ss
EDK82EV903 DE/EN/FR 5.1