5.3
Standard devices in the power range 15 ... 30 kW
5.3.1

Mains connection

(
Stop!
ƒ
ƒ
ƒ
0
PE
1
4
2,5 Nm
T1
T2
22.1 lb-in
PE
PE
L2 L3
+UG
L1
M6
+UG, -UG
5 Nm
PE
44 lb-in
EDK82EV903 DE/EN/FR 5.1
Standard devices in the power range 15 ... 30 kW
Only connect the controller to the permitted mains voltage (^ Technical
data). A higher mains voltage destroys the controller!
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
3/PE AC 400V
l
PE
+UG
L2
L3
-UG
L1
M6
L1, L2, L3
5 Nm
+UG, -UG
44 lb-in
PE
3/PE AC 400V
2-5 Nm
L1, L2,
17.7-44.3 lb-in
L3
L1 L2 L3
3
l
-UG
0
Connection for mains choke
1
Connection for footprint mains filter
2
Connection for built−on mains filter
3
Connection for braking unit^ Documentation of braking unit)
4
Temperature monitoring connection for mains filter (thermal contact
Z1
Mains choke/mains filter
l
Electrical installation
Mains connection
3/PE AC 400V
L1
L2
3
L3
N
PE
2
PE
L1' L2' L3'
Gerät / Load
PE
PE
+UG
L1
L2 L3
-UG
M6
L1, L2, L3
5 Nm
+UG, -UG
44 lb-in
PE
L1
L2 L3
Z1
T1
4
J>
T2
3
+UG
L1
L2
PE
L3
-UG
Z1
3
l
8200vec288
5
143