7
Commissioning
Selection of the control mode
Application
Stand-alone drives
with extremely alternating loads
with heavy start conditions
with speed control (speed feedback)
with high dynamic response (e. g. positioning and infeed drives)
with torque setpoint
with torque limitation (power control)
Three-phase AC reluctance motors
Three-phase sliding rotor motors
Three-phase motors with fixed frequency-voltage characteristic
Pump and fan drives with square-law load characteristic
Group drives
(several motors connected to controller)
identical motors and identical loads
different motors and/or changing loads
C0014 = -2-: linear V/f characteristic control
C0014 = -3-: square-law V/f characteristic control
C0014 = -4-: vector control
C0014 = -5-: sensorless torque control
24
EDK82EV3 DE/EN/FR 2.0
Operating mode
C0014
recommended
alternatively
-4-
-4-
-2-
-2-
-5-
-2-
-2-
-2-
-2-
-3-
-2- / -4-
-2-
-2-
L
-2-
-2-
-4-
-
-
-4-
-
-
-
-
-