7
Commissioning
The most important codes for commissioning
Code
No.
Name
C0140* Additive
frequency
setpoint
(NSET1−NADD)
C0148*
Motor parameter
s
identification
C0517*
User menu
v
1 Memory 1
2 Memory 2
3 Memory 3
4 Memory 4
5 Memory 5
6 Memory 6
7 Memory 7
8 Memory 8
9 Memory 9
10 Memory 10
146
Possible settings
Lenze
Selection
0.00
−650.00
0
0
Ready
1
Start identification
l
V/f−rated frequency (C0015), slip
compensation (C0021) and motor stator
inductivity (C0092) are calculated and
saved.
The motor stator resistance (C0084) =
l
total resistance of motor cable and
motor is measured and saved
50
C0050
Output frequency (MCTRL1−NOUT)
34
C0034
Analog setpoint selection range
7
C0007
Fixed configuration − digital input signals
10
C0010
Minimum output frequency
11
C0011
Maximum output frequency
12
C0012
Acceleration time main setpoint
13
C0013
Deceleration time main setpoint
15
C0015
V/f rated frequency
16
C0016
U
boost
min
2
C0002
Parameter set transfer
{0.02 Hz}
650.00
EDK82EV222 DE/EN/FR 10.1
IMPORTANT
j
Selection via function
l
keypad or the parameter channel
Is added to main setpoint
l
l
Value is stored when switching the
mains or removing the keypad
Only when the motor is cold!
1. Inhibit controller, wait until drive is
at standstill
2. Enter the correct motor data under
C0087, C0088, C0089, C0090,
C0091 (see motor nameplate).
v
3. Set C0148 = 1 by
4. Enable controller
The identification
c
– starts,
goes off
– the motor makes a high−pitched
tone, but does not rotate!
– takes approx. 30 s
c
– is completed when
again
5. Inhibit controller
After mains switching or when
l
g
using the function
the code
from C0517/1 will be displayed.
In Lenze setting, the user menu
l
contains the most important codes
for starting−up the control mode
"V/f characteristic control with
linear characteristic"
When the password protection is
l
activated, only the codes entered
under C0517 are freely accessible.
Enter the required code numbers in
l
the subcodes.
Codes, which are only active when
being used together with an
Application−I/O, cannot be entered!
L