Code
No.
Name
C0034*
Setpoint
v
selection range
Application I/O
(A)
uSEr
1 X3/1U, X3/1I
2 X3/2U, X3/2I
C0037
JOG1
C0038
JOG2
C0039
JOG3
C0087
Rated motor
speed
C0088
Rated motor
current
C0089
Rated motor
frequency
C0090
Rated motor
voltage
Motor cos ϕ
C0091
C0119
Configuration of
v
motor
temperature
−33−
monitoring (PTC
input) / earth
fault detection
L
The most important codes for commissioning
Possible settings
Lenze
Selection
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
1
Bipolar voltage −10 V ... +10 V
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
4
Current 4 ... 20 mA open−circuit monitored
20.00 −650.00
30.00 −650.00
40.00 −650.00
à
300
à
0.0
50
10
à
50
à
0.40
0
0
PTC input not active
1
PTC input active,
TRIP set
2
PTC input active,
Warning set
3
PTC input not active
4
PTC input active,
TRIP set
5
PTC input active,
Warning set
EDK82EV222 DE/EN/FR 10.1
650.00 JOG = fixed setpoint
{0.02 Hz}
{0.02 Hz}
650.00
{0.02 Hz}
650.00
{1 rpm}
16000
{0.1 A}
650.0
{1 Hz}
960
{1 V}
500
{0.1}
Earth fault detection
active
Earth fault detection
inactive
Commissioning
IMPORTANT
Observe the jumper setting of the
function module!
Minimum output frequency (C0010)
not effective
Changing the direction of rotation is
only possible with a digital signal.
Changing the direction of rotation is
only possible with a digital signal.
TRIP Sd5 if I < 4 mA
Additional fixed setpoints
à
Depending on the controller
à
Depending on the controller
0.0 ... 2.0 x rated output current of the
controller
à
230 V with 230 V controllers,
400 V with 400 V controllers
1.0
à
Depending on the controller
Signal output configuration under
l
C0415
If several parameter sets are used,
l
the monitoring must be separately
adjusted for each parameter set.
l
Deactivate the earth fault
detection, if it has been activated
unintentionally.
If the earth fault detection is active,
l
the motor starts after controller
enable with a delay of approx.40
ms.
7
ð