Fault detection and elimination
Fault messages
1)
Keypad
PC
Error
DC−bus overvoltage
OU
c
(Warning or TRIP
configurable under
22
OUE
C0310)
a
75
Faulty parameter
Pr
a
transfer when using
the keypad
72
Wrong PAR1 transfer
Pr1
a
when using the
keypad.
73
Wrong PAR2 transfer
Pr2
a
when using the
keypad.
77
Wrong PAR3 transfer
Pr3
a
when using the
keypad.
78
Wrong PAR4 transfer
Pr4
a
when using the
keypad.
79
Internal fault
Pr5
a
81
Time fault during
Pt5
a
parameter set transfer
76
Faulty auto−TRIP reset
rSt
a
85
Wire breakage analog
sd5
a
input 1
87
Wire breakage analog
sd7
a
input 2
1)
LECOM−fault number, display in parameter setting program Global Drive Control (GDC)
154
Cause
Mains voltage too high
Braking operation
Earth leakage on the motor side
All parameter sets are defective
PAR1 is defective.
PAR2 is defective.
PAR3 is defective
PAR4 is defective
EEPROM is defective
Data flow from keypad or PC
interrupted, e. g. keypad was
disconnected during transfer
More than 8 fault messages in 10
minutes
Current at analog input < 4 mA at
setpoint range 4 ... 20 mA
EDK82EV222 DE/EN/FR 10.1
Remedy
Check voltage supply
Prolong deceleration times.
l
l
Operation with external brake resistor:
– Check dimensioning, connection and
cable of the brake resistor.
– Increase the deceleration times
Check motor cable and motor for earth fault
(disconnect motor from inverter)
It is absolutely necessary to repeat the data
transfer or load the Lenze setting before
enabling the controller.
Contact Lenze
It is absolutely necessary to repeat the data
transfer or load the Lenze setting before
enabling the controller.
Depends on the error message
Close circuit at analog input