7
Commissioning
Using the keypad XT EMZ9371BC − Linear V/f characteristic control
Switch−on sequence
8.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
9.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10.
Set the acceleration time T
Lenze setting: 5.00 s
11.
Set the deceleration time T
Lenze setting: 5.00 s
12.
Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz
13.
Set the V
boost (C0016)
min
Lenze setting: dependent on the controller type
14.
Activate the motor temperature monitoring
(C0119) if a PTC or thermal contact is
connected to the terminal X2.2.
Lenze setting: switched−off
15.
Setpoint selection
16.
Enable the controller.
17.
The drive should be running now
)
Note!
In the menu "Diagnostic" the most important drive parameters can be
monitored
132
C0011
C0010
(C0012)
ir
f [ H z ]
C 0 0 1 1
f 2
f 1
(C0013)
if
0
V
out
100%
V
e. g. via potentiometer at the
terminals 7, 8, 9
EDK82EV222 DE/EN/FR 10.1
[f]
0 %
100 %
t i r
t i f
T i r
T i f
min
0
f
0
C0015
X3
20
28
misc002
Note
C0011
+ t
@
T
ir
ir
f 2 * f 1
t
= acceleration time wanted
ir
C0011
+ t
@
T
t
f 2 * f 1
if
if
t
= deceleration time wanted
if
The Lenze setting is suitable for all
common applications
Setting possibilities: (^ 145)
Terminal X3/28 = HIGH
CW rotation: X3/E4 = LOW
CCW rotation: X3/E4 = HIGH
If the drive does not start, press