1)
Keypad
PC
Error
0
No fault
noer
71
System fault
ccr
a
61
Communication fault to
ce0
a
AIF
(configurable in C0126)
62
Communication fault to
ce1
a
CAN−IN1 with Sync
control
63
Communication error to
ce2
a
CAN−IN2
64
Communication error to
ce3
a
CAN−IN1 with event or
time control
65
BUS−OFF
ce4
a
(many communication
faults occurred)
66
CAN Time−Out
ce5
a
(configurable in C0126)
67
Function module
ce6
a
system bus (CAN) on
FIF has set "Warning"
or "BUS−OFF"
(configurable in C0126)
L
Fault detection and elimination
Cause
Strong interferences on control cables Shield control cables
Ground or earth loops in the wiring
Faulty transmission of control
commands via AIF
CAN−IN1 object receives faulty data or
communication is interrupted
CAN−IN2 object receives faulty data or
communication is interrupted
CAN−IN1 object receives faulty data or
communication is interrupted
Controller has received too many
incorrect telegrams via the system
bus and has been disconnected
For remote parameter setting via
system bus (C0370):
Slave does not answer.
Communication monitoring time
exceeded.
For operation with application I/O:
Faulty parameter setting of parameter
set changeover
For operation with module in FIF:
Internal fault
CAN controller sets "Warning" or "BUS
OFF"
EDK82EV222 DE/EN/FR 10.1
Fault messages
Remedy
Insert the communication module into the
hand terminal
Plug−in connection − bus module
l
Check FIF
Check transmitter
l
l
Increase monitoring time under C0357/1
if necessary
Plug−in connection − bus module
l
Check FIF
Check transmitter
l
Increase monitoring time under C0357/2
l
if necessary
Plug−in connection − bus module
l
Check FIF
Check transmitter
l
Increase monitoring time under C0357/3
l
if necessary
Check whether bus terminator available
l
l
Check screen contact of the cables
Check PE connection
l
Check bus load, if necessary, reduce the
l
baud rate
l
Check system bus wiring
Check system bus configuration
l
In all parameter sets the signal "parameter
set changeover" (C0410/13, C0410/14)
must be combined with the same source
Contact Lenze
Check whether bus terminator available
l
Check screen contact of the cables
l
l
Check PE connection
Check bus load, if necessary, reduce the
l
baud rate
8