Lenze 8200 vector Instructions De Montage page 134

Masquer les pouces Voir aussi pour 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7
Commissioning
Using the keypad XT EMZ9371BC − Vector control
Switch−on sequence
8.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
9.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10.
Set the acceleration time T
Lenze setting: 5.00 s
11.
Set the deceleration time T
Lenze setting: 5.00 s
12.
Set the control mode "Vector control" (C0014 =
4)
Lenze setting: Linear V/f characteristic control
(C0014 = 2)
13.
Enter the motor data
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: Depending on the controller
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: Depending on the controller
E
Motor−cosj (C0091)
Lenze setting: Depending on the controller
134
C0011
C0010
(C0012)
ir
f [ H z ]
C 0 0 1 1
f 2
f 1
(C0013)
if
0
EDK82EV222 DE/EN/FR 10.1
[f]
0 %
100 %
t
t i r
t i f
T i r
T i f
SHPRG
Menu
0014
00
Code
Para
4
V e c t o r - C t r l
9371BC008
Note
C0011
+ t
@
T
ir
ir
f 2 * f 1
t
= acceleration time wanted
ir
C0011
+ t
@
T
f 2 * f 1
if
if
t
= deceleration time wanted
if
See motor nameplate
Enter the value for the motor
connection type (star/delta) selected!
Enter the value for the motor
connection type (star/delta) selected!