When P41 is equal to 0 (standard effect) and the servomotor
control output is configured, the following conditions may occur:
- The instrument detects an OVERRANGE and a reverse action
is assigned to the servomotor output, the OUT 1 ( ) turns OFF
while OUT 2 ( ) turns ON.
- The instrument detects an OVERRANGE and a direct action
is assigned to the servomotor output, the OUT 1 ( ) turns
ON while OUT 2 ( ) turns OFF.
- The instrument detects an UNDERRANGE and a reverse
action is assigned to the servomotor output, the OUT 1 ( )
turns ON while OUT 2 ( ) turns OFF.
- The instrument detects an UNDERRANGE and a direct
action is assigned to the servomotor output, the OUT 1
( ) turns OFF while OUT 2 ( ) turns ON.
The sensor leads break can be signalled as:
- for TC/mV input
:
OVERRANGE or UNDERRANGE
selected by a solder jumper
- for RTD input
:
OVERRANGE
- for mA/V input
:
UNDERRANGE
Note: On the mA/V input the leads break can be detected
Note
Note
Note
Note
only when the range selected has a zero elevation (4/20
mA or 1/5 V or 2/10 V)
On RTD input a special test is provided to signal
OVERRANGE when input resistance is less than 15 ohm
(Short circuit sensor detection).
XKSser1-B0.PMD
24
ERROR
ERROR
ERROR
ERROR
ERROR
MESSAGES
MESSAGES
MESSAGES
MESSAGES
MESSAGES
The instrument performs same self-diagnostic algorithm.
When an error is detected, the instrument shows on the lower
display the "Err" indication while the upper display shows the
code of the detected error.

ERROR LIST

ERROR LIST
ERROR LIST
ERROR LIST
ERROR LIST
SEr
Serial interface parameter error
100
Write EEPROM error.
150
CPU error.
200
Tentative to write on protected memory.
201 - 2xx
Configuration parameter error. The two less
significant digit's shown the number of the
wrong parameter (ex. 209 Err show an Error
on P9 parameter)
299
Error in control outputs selection
301
Error on calibration of the selected input
302
Feedback potentiometer calibration error
307
RJ input calibration error
400
Control parameters error
500
Auto-zero error
502
RJ error
510
Error during calibration procedure
512
Error during feedback calibration procedure.
N O T E
N O T E
N O T E
N O T E
N O T E
1) When a configuration parameter error is detected, it is
sufficient to repeat the configuration procedure of the
specify parameter.
2 ) If error 400 is detected, push contemporarily the
and
pushbuttons for loading the default parameters
then repeat control parameter setting.
3 ) When an error 302 is detected, push contemporarily
the
and
pushbuttons for loading the default
feedback potentiometer calibration values then repeat
the feedback potentiometer calibration.
4 ) For all the other errors, contact your supplier.