18 = V
Linear
range
1 /
19 = V
Linear
range
0 /
20 = V
Linear
range
2 /
21 = TC type
L
range
0 /
22 = TC type
J
range
-150 /
23 = TC type
K
range
-150 /
24 = TC type
T
range
-330 /
25 = TC type
N
range
-150 /
26 = TC type
R
range
0 /
27 = TC type
S
range
0 /
28 = TC type
B
range
0 /
29 = RTD type
Pt 100
range
-199.9 /
30 = RTD type
Pt 100
range
-330 /
NOTE
NOTE
NOTE
NOTE: selecting P1 = 0, 2, 4, 6, 10,11, 28 or 29, the
NOTE
instrument set automatically P43 = FLtr. For all the
remaining ranges it will set P43 = nOFL.
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
P2 = Decimal point position
This parameter is available only when a linear input is
selected (P1 = 13, 14, 15, 16, 17, 18, 19 or 20).
----.
= No decimal figure.
---.-
= One decimal figure.
--.--
= Two decimal figures.
-.---
= Three decimal figures.
P3 = Initial scale value
P3 = Initial scale value
P3 = Initial scale value
P3 = Initial scale value
P3 = Initial scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD input it is programmable within the input
range.
Notes:
Notes:
Notes:
Notes:
Notes:
1) When this parameter is modified, rL parameter will be
re-aligned to it.
2) If a linear input is selected, the value of this parameter
can be greater than P4 in order to get a reverse
readout.
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
P4 = Full scale value
For linear inputs it is programmable from -1999 to 4000.
For TC and RTD inputs, it is programmable within the
input range.
Notes:
Notes:
Notes:
Notes:
Notes:
1) When this parameter is modified, rH parameter will be
re-aligned to it.
XKSser1-B0.PMD
9
5 V
2) If a linear input is selected, the value of this parameter
10 V
can be smaller than P3 in order to get a reverse
10 V
readout.
The initial and full scale values determine the input span
+1650 °F
which is used by the PID algorithm, the SMART and the
+1830 °F
+2500 °F
alarm functions.
NOTE
NOTE
+750 °F
NOTE
NOTE
NOTE: the minimum input span (S = P4 - P3), in absolute
value, should be set as follows:
+2550 °F
- For linear inputs, S > 100 units.
+3200 °F
- For TC input with °C readout, S > 300 °C.
+3200 °F
+ 3310 °F
- For TC input with °F readout, S > 550 °F.
+400.0 °F
- For RTD input with °C readout, S > 100 °C.
- For RTD input with °F readout, S > 200 °F.
+1470 °F
P5 = Output 1 type
P5 = Output 1 type
P5 = Output 1 type
P5 = Output 1 type
P5 = Output 1 type
Sñ.OL= servomotor open loop.
Sñ.CL = servomotor close loop.
rEv = time proportional control output with reverse action
dir = time proportional control output with direct action.
Reverse
INPUT
INPUT
t
OUTPUT
OUTPUT
t
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
1 ) If P5 is changed to "Sñ.OL" or it is changed from
"Sñ.OL" to another selection, the parameter P41 will
be forced to 0.
2 ) If P5 is changed to "rEv" the cycle time (Cy1) will be
forced to 15 s
3 ) If P5 is changed to "dir" the cycle time (Cy1) will be
forced to:
10 s when P25 = Air
4 s when P25 = OIL
2 s when P25 = H2O
GB
GB
GB
GB
GB
9