OPEN INPUT CIRCUIT
OPEN INPUT CIRCUIT
OPEN INPUT CIRCUIT
OPEN INPUT CIRCUIT
OPEN INPUT CIRCUIT
This instrument is able to identify the open circuit for TC
and RTD inputs.
The open input circuit condition for RTD input is shown by
an "overrange" indication.
For TC input, it is possible to select overrange indication
(standard) or underrange indication setting the CH2 and SH2
according to the following table:
Overrange (STD)
CH2 = close
SH2 = open
Underrange
CH2 = open
SH2 = close
Both pads are located on the soldering side of the CPU
card
SH2
CH2
XKSser1-B0.PMD
7
INSTRUMENT
INSTRUMENT
INSTRUMENT
INSTRUMENT
INSTRUMENT CONFIGURATION
CONFIGURATION
CONFIGURATION
CONFIGURATION
CONFIGURATION
1) Switch on the instrument.
The upper display shows the measured value while the lower
display shows the programmed set point value (we define the
above condition as "normal display mode").
2) Push "FUNC" pushbutton and, maintaining the pressure,
push the "MAN" pushbutton for more than 4 seconds.
The lower display will show "ConF" while the upper display
will show "C.ñOn".
NOTE: two different configuration mode are possible:
NOTE
NOTE
NOTE
NOTE
A) Monitor mode
Monitor mode
Monitor mode
Monitor mode: in this mode it is possible to monitor
Monitor mode
but not to modify the configuration parameter. During
the monitor mode the instrument continue to perform
the standard control.
B) Modify mode
Modify mode
Modify mode: in this mode it is possible to verify
Modify mode
Modify mode
and to modify all configuration parameter.
3) By
and
pushbuttons select the "C.ñOd" indication
(modify mode).
4 ) Push the "FUNC" pushbutton.
NOTES:
NOTES
NOTES
NOTES
NOTES
1 ) When modify mode is started, the instrument stops the
control action and:
- sets control outputs to OFF;
- sets alarms in no alarm condition;
- disables the serial link.
2 ) If the configuration is protected by security code the
display will show:
By
and
keys enter a value equal to the
configuration security code (see P55 parameter) or the
master key code (see appendix A).
Note:
Note:
Note:
Note:
Note: the master key code allows to enter in modify
configuration parameters mode either if the configuration
security code is lost or if the configuration parameters are
always protected (P55 = 1).