When it is desired to exit from configuration modify mode
proceed as follows:
a) Push "FUNC" or "MAN" push-button more times until the
"C.End" parameter is displayed.
b) Pushing " " or " " push-button select the "YES"
indication.
c) Push "FUNC" push-button. The instrument ends the
configuration modify mode, preforms an automatic
reset and restarts in the run time mode.
Pushbutton function during configuration mode
Pushbutton function during configuration mode
Pushbutton function during configuration mode
Pushbutton function during configuration mode
Pushbutton function during configuration mode
FUNC =
This will memorize the new value of the
selected parameter and go to the next
parameter (increasing order).
MAN =
This will scroll back the parameters without
memorization of the new value.
=
This will increase the value of the selected
parameter
=
This will decrease the value of the selected
parameter.

CONFIGURATION PARAMETERS

CONFIGURATION PARAMETERS
CONFIGURATION PARAMETERS
CONFIGURATION PARAMETERS
CONFIGURATION PARAMETERS
Notes:
Notes:
Notes:
Notes:
Notes:
1 ) In the following pages we will describe all the
parameters of the instrument but the instrument will
show only the parameters related with the specific
hardware and in accordance with the specific
instrument configuration (i.e. setting OUT 3 (P7) =
nonE, (not used), all the parameters related with this
output will not be displayed).
2 ) During configuration mode, the lower display shows
the mnemonic code of the selected parameter while
the upper display shows the value or the status
assigned to the selected parameter.
dF.Cn = Load default configuration data
dF.Cn = Load default configuration data
dF.Cn = Load default configuration data
dF.Cn = Load default configuration data
dF.Cn = Load default configuration data
OFF
= No default data loading
tb.1
= Load table 1 default data loading (european)
tb.2
= Load table 2 default data loading (american)
For more datails see appendix A.
XKSser1-B0.PMD
8
SEr1 = Serial interface protocol
SEr1 = Serial interface protocol
SEr1 = Serial interface protocol
SEr1 = Serial interface protocol
SEr1 = Serial interface protocol
OFF
= No serial interface
Ero
= Polling/selecting ERO
ñbUS
= Modbus
jbUS
= Jbus
SEr2 = Serial link device address
SEr2 = Serial link device address
SEr2 = Serial link device address
SEr2 = Serial link device address
SEr2 = Serial link device address
Not available when SEr1 = OFF
From 1 to 95 for ERO protocol
From 1 to 255 for all the other protocols
NOTE
NOTE
NOTE
NOTE
NOTE: the electrical characteristic of the RS 485 serial
interface will allow the connection of 31 devices maximum.
SEr3 = Baude rate for serial link
SEr3 = Baude rate for serial link
SEr3 = Baude rate for serial link
SEr3 = Baude rate for serial link
SEr3 = Baude rate for serial link
Not available when SEr1 = OFF
From 600 to 19200 baud.
NOTE: 19200 baud is shown on display as 19.2.
NOTE
NOTE
NOTE
NOTE
SEr4 = Byte format for serial link
SEr4 = Byte format for serial link
SEr4 = Byte format for serial link
SEr4 = Byte format for serial link
SEr4 = Byte format for serial link
Not available when SEr1 = OFF
7E
= 7 bits + even parity (For ERO protocol only)
7O = 7 bits + odd parity (For ERO protocol only)
8E
= 8 bits + even parity
8O = 8 bits + odd parity
8
= 8 bits without parity
P1 - Input type and standard range
P1 - Input type and standard range
P1 - Input type and standard range
P1 - Input type and standard range
P1 - Input type and standard range
0
= TC type
L
range
1
= TC type
L
range
2
= TC type
J
range -100.0 /
3
= TC type
J
range
-100 /
4
= TC type
K
range -100.0 /
5
= TC type
K
range
-100 /
6
= TC type
T
range -199.9 /
7
= TC type
N
range
-100 /
8
= TC type
R
range
9
= TC type
S
range
10 = TC type
B
range
11 = RTD type
Pt 100
range -199.9 /
12 = RTD type
Pt 100
range
-200 /
13 = mV
Linear
range
14 = mV
Linear
range
15 = mA
Linear
range
16 = mA
Linear
range
17 = V
Linear
range
GB
GB
GB
GB
GB
8
12/09/2005, 9.46
0 /
+400.0 °C
0 /
+900 °C
+400.0 °C
+1000 °C
+400.0 °C
+1370 °C
+400.0 °C
+1400 °C
0 /
+1760 °C
0 /
+1760 °C
0 /
+1820 °C
+400.0 °C
+800 °C
0 /
60 mV
12 /
60 mV
0 /
20 mA
4 /
20 mA
0 /
5 V

Publicité