P50 - Set point access
P50 - Set point access
P50 - Set point access
P50 - Set point access
P50 - Set point access
0
only SP is accessible.
1
only SP and SP2 are accessible.
2
all 4 set points are accessible.
P51 = "Loop break alarm" function.
P51 = "Loop break alarm" function.
P51 = "Loop break alarm" function.
P51 = "Loop break alarm" function.
P51 = "Loop break alarm" function.
dIS =
Alarm not used
Enb =
The alarm condition of the "Loop break alarm"
(LBA) will be shown by the OUT 4 LED only.
EnbO = The alarm condition of the "Loop break alarm"
(LBA) will be shown by the OUT 4 LED and by
the OUT 4 relay status.
NOTES
NOTES
NOTES:
NOTES
NOTES
1 ) When the loop break alarm is enabled, the alarm 3 will
be automatically disabled.
2 ) The alarm 2, the alarm 3 and the "Loop break alarm"
are in OR condition on the same output (OUT 4).
3 ) The OUT 4 action type is programmed by P28
parameter.
4 ) The loop break alarm reset type is programmed by
P12 parameter.
5 ) For more details see "Loop Break Alarm function" at
pag 19.
P52 = Loop break alarm deviation
P52 = Loop break alarm deviation
P52 = Loop break alarm deviation
P52 = Loop break alarm deviation
P52 = Loop break alarm deviation
This parameter is available only when P51 is different
from "diS".
Range: from 0 to 500 units.
P53 =
P53 =
Loop break alarm time.
Loop break alarm time.
P53 =
P53 =
P53 =
Loop break alarm time.
Loop break alarm time.
Loop break alarm time.
This parameter is available only when P51 is different
from "dIS".
Programmable from 00.01 to 40.00 mm.ss.
P54 = Loop break alarm hysteresis.
P54 = Loop break alarm hysteresis.
P54 = Loop break alarm hysteresis.
P54 = Loop break alarm hysteresis.
P54 = Loop break alarm hysteresis.
This parameter is available only when P51 is different
from "dIS".
Programmable from 1to 50% of the power output.
XKSser1-B0.PMD
15
P55 =
P55 = Security code for configuration
P55 =
P55 =
P55 =
Security code for configuration
Security code for configuration
Security code for configuration
Security code for configuration
p a r a m e t e r s
p a r a m e t e r s
p a r a m e t e r s
p a r a m e t e r s
p a r a m e t e r s
0
No protection (it is always possible to modify all
configuration parameters);
1
Always protected (it is not possible to modify any
configuration parameter);
from 2 to 9999 security code for configuration parameter
protection.
Notes:
Notes:
Notes:
Notes:
Notes:
1) If a value from 2 to 9999 has been assigned as security
code it cannot be displayed anymore, when returning
on this parameter the display will show "On".
2) If the security code is forgotten a master key code is
available, by this code it is ever possible to enter in
modify configuration mode (S.CnF = 1 or from 2 to
9999).
The master key code is located in Appendix A.
Fill out and cut the part of the Appendix A reserved to
the security codes if it is desired to keep them secrets.
C. End = End configuration
C. End = End configuration
C. End = End configuration
C. End = End configuration
C. End = End configuration
This parameter allows to come back to the run time mode.
NO =
the instrument remains in configuration mode and
comes back to the first display of the configura-
tion mode (dF.Cn).
YES = This selection ends the configuration mode. the
instrument performs an automatic reset and
restart the run time mode.
GB
GB
GB
GB
GB
15