Programming the Unit
The 301EM is equipped with a programming menu that allows users to modify certain parameters and to cali-
brate the unit.
Menu Option
Password
Provides password restricted access to programming menus
Set Adr.
Let's users select a specific address for the device
Mem SD
Inactive option: Reserved for technicians' use only
Sensor
Let's users add or remove a sensor
Set #RP
Let's users add up to ten 301EMRP units
Service
Let's users specify different Service alarm settings
SetEvent
Let's users configure specific events for some or all sensor types
SetRelay
Let's users specify whether a relay will be set to failsafe
Buzzer
Let's users activate or deactivate the silence button
Set Alr
Let's users set specific minimum and maximum alarm levels (for alarms A, B and C)
SetAnOut
Let's users adjust the 4-20 outputs
Set Zero
Let's users adjust the sensor zero
Set Span
Let's users calibrate each sensor
Quit
Let's users exit the programming menus
Accessing the Programming Menus
Access to the 301EM's programming is password protected for security reasons. The password is "VA".
Press the enter key to access the programming menus. The PASSWORD screen is displayed
The first letter is underlined. Press the up or down arrow to change the letter until V is displayed
Press Enter to confirm. The next letter is underlined. Press the up or down arrow until A is displayed
Press Enter to confirm the password and access the menus
Setting the Unit's Address for Communications with 301C Controller
The 301EM is shipped with the default address set to 1. If you are using the unit in a network, this menu lets
you select a specific address, per your network configuration.
Access the menu and use the arrows to scroll to the Set Adr. menu and press enter to select.
The Set Adr. menu is displayed. Use the arrows to change the address and press enter when the de-
sired address (Modbus addresses M001 to M254 and Vulbus addresses V01 to V30) is displayed.
The screen returns to the main menu
Make certain that no two devices share an address