Objects; Device Object - Honeywell 301 Serie Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Objects

Device Object

Property
Object_identifier
Object_type
Vendor_identifier
Apdu_timeout
Application_software_version
Firmware_revision
Max_apdu_length_accpeted
Model_name
Numer_of_apdu_retries
Object)name
Protocol_object_types_support
Protocol_services_supported
Protocol_version
Segmentation_supported
System_status
Vendor_names
Protocol_revision
Database_revision
Note:
1 -
indicates that this property is required by ASHRAE
"R"
-
Standard 135
indicates that this property is optional by ASHRAE
"O"
Standard 135
2 -
Indicates that this property is hard-coded as a con-
"C"
-
stant
indicates that this property is stored in non-volatile
"N"
memory
indicates that this property is computed constantly
"R"
and stored in RAM
111
Data Type
Required
Unsigned
R
Enumerated
R
Enumerated
R
Unsigned
R
Character string
R
Character string
R
Unsigned
R
Character string
R
Unsigned
R
Character string
R
Bit string
R
Bit string
R
Unsigned
R
Enumerated
R
Enumerated
R
Character string
R
Unsigned
R
Unsigned
R
Storage
BACnet
1
type
writeable?
2
N
N
C
N
C
N
C
N
C
N
C
N
C
N
C
N
C
N
N
N
C
N
C
N
C
N
C
N
C
N
C
N
C
N
C
N
Value
Set form LUI
Device (8)
Honeywell Inc. (17)
0
"1.1"
"1.4.9"
1476
"301C-BIP"
0
Default "VAC301C:1", settable from LUI
Device, analog_input, and binary_input.
If configured, analog_value object ap-
pear, bur is outside of BTL approval.
Read property, read property multiple,
write property, who_has, who_is
1
No_segmentation (3)
Operational (0)
Honeywell
7
Increments as objects added

Publicité

Table des Matières
loading

Table des Matières