These menus appear only for certain devices.
Scale(1) allows the detection range, minimum and maximum, to be defined for the
selected device. Whatever value is specified is the value that will appear at the de-
vice display (if applicable). The Minimum value is generally left at 0. Parameters
for the XNX and XCD gas detectors can be viewed here but can be changed only
at the transmitter.
1. Tx info
-Scale (1)-
Max
00250
Min
00000
Scale(2) allows the factor by which to divide the scale (between 0 and 65535) and
the unit of measurement for the selected scale to be determined.
1. Tx info 001
-Scale (2)-
Factor
00010
Units
%
The factor allows precise scale limits for detection to be set. By dividing the maxi-
mum scale value in the first Scale screen (250 in this example) by 10, a scale value
of 25.0 can then be displayed.
The "Units" allow the device's unit of measurement to be selected:
°F = Sets degree Fahrenheit as the unit of measurement
°C = Sets degree Centigrade as the unit of measurement
%RH = Sets Relative Humidity as the unit of measurement
mV = Sets millivolts as the unit of measurement
V = Sets volts as the unit of measurement
mA = Sets milliamps as the unit of measurement
% = Sets the percentage of gas as the point unit of measurement
ppm = Sets parts per million of gas as the point unit of measurement