Enables each output to be activated and validates operation of each con-
Test
troller keypad buttons, display pixels, and various communication proto-
sequence
cols.
Selecting this option starts the Simulation mode. While in simulation
mode, events are not logged because this mode deactivates network com-
munication Information Updates. It can be combined with any of the three
previous modes (example: using the Simulation mode when in Debug
mode allows the user to test the entire system [groups, events, etc.] with-
out triggering any actions or using any additional material such as gases).
It allows gas concentrations to be simulated over an associated scale for
each transmitter, sequentially:
Alarm levels A, B and C are evaluated per the simulated gas concentra-
Start Sim
tion and events are evaluated and actions are taken.
Sequence
This type of alarm simulation at the controller does not work with certain
transmitters with falling alarms. In these cases, an alarm can be simulated
at the transmitter.
The Start Sim Sequence will not function for 420I outputs that use a
Virtual Address, and the transmitter(s) within a Virtual Group will need to
be tested with actual gas for the output in the 420I to function properly.
While in simulation mode, the controller is unaware of the device's actual
network status. This mode can be stopped at any time in the Test menu
(see Normal System Operation).
If one of these modes has been activated, the system will automatically re-
turn to Normal Mode after 12 hours of inactivity. (No changes will be lost.)
Activates all controller components.
Maximum
load
Normal controller operation mode. This is the system's normal (default)
operation mode. When the system is in normal mode, some values can be
changed without interrupting services. When a value has been changed in
Normal
any of the menu fields, the change will take effect upon returning to the
main menu screen.
Setting
Activates the polling mode on a single transmitter. This mode allows
transmitters to be analyzed one at a time. The controller polls only the
Single Tx
selected device, which subsequently has its information updated. This
mode does not interfere with Event Evaluation functions.
Activates the service mode to perform a calibration and to test Events
without triggering actions.
Debug
This mode allows complete system operation to be evaluated and
tested without affecting operations (outside of debug mode). Events are
evaluated and displayed as necessary but no action is triggered.