S301-D2

Wiring Details

The drawing below illustrates the connection for a S301-D2 sensor with the D2RS-PC option.
Communication: Use 2-24 AWG, twisted and shielded cable (Belden 9841 or equivalent)
Power: Use 2-18 AWG cable, maximum length of 160 m (500 ft.).
101
+VDC RED
24
IN
GND
BLACK
V+
V-
A
sensor #1
sensor #2
POWER:
sensor #3
Maximum 4 power
connections direct to unit.
Additional power sources
required for every group of 4
sensors.
COMMUNICATION:
Communication must be
connected in daisy chain
configuration.
A
B
J17
WHITE
GREEN
sensor #4
Power
Comm.
sensor #5
External
V- (black)
Power
Supply
V+ (red)
sensor #6
HPTV5DC8,
Input: 115 VAC 1A,
Output: 4.0A@6 and
12VDC, 2.5A@ 24VDC
sensor #7
sensor #8
A
B
(white)
(green)
To next
sensors