4-20 Output Configuration

4-20 mA Current Sourcing Output Configuration

The transmitter supplies the loop current. The maximum impedance supported by the loop is 400 ohms.
Set jumpers on JP4 at 1-2, 3-4 and 5-6.
A dedicated power supply must be used with
each 301EM. Considerable damage may occur
if this condition is not strictly followed.
Current Sourcing Output Configuration
24 VAC
24 VAC
LEGE ND
- ONE TRANSMITTE R CO NNECTE D
- MORE THAN ONE TRANSMITTER CO NNECTE D
85
TRANSMITTER 1
24 VAC
4-20 mA
J16
J9
+4@20
-4@20
V+ V-
TRANSMITTER X
4-20 mA
24 VAC
J16
J9
+4@20
-4@20
V+ V-
DDC SYSTEM