Lenze Global Drive 8200 vector Instructions De Montage page 143

Convertisseur de fréquence
Masquer les pouces Voir aussi pour Global Drive 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Show/Hide Bookmarks
Code
No.
Name
C0410
Free configuration of
v
digital input signals
1 NSET1-JOG1/3
NSET1-JOG1/3/5/7
(A)
2 NSET1-JOG2/3
NSET1-JOG2/3/6/7
(A)
3 DCTRL1-CW/CCW
4 DCTRL1-QSP
5 NSET1-RFG1-STOP
6 NSET1-RFG1-0
7 MPOT1-UP
8 MPOT1-DOWN
9 Reserved
10 DCTRL1-CINH
11 DCTRL1-TRIP-SET
12 DCTRL1-TRIP-RESET
13 DCTRL1-PAR2/4
14 DCTRL1-PAR3/4
15 MCTRL1-DCB
16 (A) PCTRL1-RFG2-
LOADI
17 DCTRL1-H/Re
18 PCTRL1-I-OFF
19 PCTRL1-OFF
20 Reserved
21 PCTRL1-STOP
22 DCTRL1-CW/QSP
23 DCTRL1-CCW/QSP
24 DFIN1-ON
L
Possible settings
Lenze
Selection
Linkage of external signal sources to internal digital
signals
Digital signal source
1
0
Not assigned (FIXED-FREE)
255
2
1 ... 6
Digital inputs X3/E1 ... X3/E6 (DIGIN1 ... 6)
X3/E1 (1) ... X3/E6 (6)
E5, E6 only application I/O
4
7
PTC input (X2.2/T1, X2.2/T2)
255
10 ... 25
AIF control word (AIF-CTRL)
Bit 0 (10) ... bit 15 (25)
255
255
30 ... 45
CAN-IN1.W1/FIF-IN.W1
Bit 0 (30) ... bit 15 (45)
255
CAN-IN1.W2/FIF-IN.W2
255
50 ... 65
Bit 0 (50) ... bit 15 (65)
255
255
255
70 ... 85
CAN-IN2.W1
Bit 0 (70) ... bit 15 (85)
255
255
90 ... 105
CAN-IN2.W2
Bit 0 (90) ... bit 15 (105)
255
140 ...
Status application I/O
172
as C0415, selection 140 .. 172
3
200
Bit-by-bit assignment of the FIF control words
y
g
(FIF-CTRL1, FIF-CTRL2) from the function module
(FIF CTRL1 FIF CTRL2) f
255
INTERBUS or PROFIBUS-DP (see C0005)
255
201 ...
255
Digital output signals
231
231
255
201
as C0415, selection 1
255
...
...
255
231
as C0415, selection 31
255
255
255
EDK82EV903 DE/EN/FR 1.0
Commissioning
(
)
h f
i
d l
Code table
IMPORTANT
A selection made under C0007 is copied
to the corresponding subcode of C0410.
A change of C0410 sets C0007 = 255!
Selection of fixed setpoints
C0410/1
C0410/2
active
C0410/33
C0046
LOW
LOW
LOW
LOW
LOW
LOW
JOG1
JOG1
HIGH
LOW
LOW
JOG2
LOW
HIGH
LOW
...
...
...
...
JOG7
HIGH
HIGH
HIGH
CW = CW rotation
LOW
CCW = CCW rotation
HIGH
Quick stop (via terminal LOW active)
Ramp function generator main setpoint stop
Ramp function generator input must be set "0"
for mains setpoint
Motor potentiometer functions
p
Controller inhibit (via terminal LOW active)
External error (via terminal LOW active)
Error reset
Parameter set changeover
(only possible, if C0988 = 0)
C0410/13 and C0410/14 must have the same
source in everey parameter sets used.
Otherwise it is not possible to change
between the parameter sets.
C0410/13
C0410/14
active
LOW
LOW
PAR1
HIGH
LOW
PAR2
LOW
HIGH
PAR3
HIGH
HIGH
PAR4
DC-injection brake
Actual process controller value (PCTRL1-ACT)
must be connected to process controller ramp
function generator (PCTRL1-RFG2)
Manual/remote changeover
Process controller switch off
Process controller stop (value "frozen")
Failsafe change of the direction of rotation
g
0 = Frequency input not active
1 = Frequency input active
Frequency input configuration under C0425 and
C0426
65

Publicité

Table des Matières
loading

Table des Matières