Lenze Global Drive 8200 vector Instructions De Montage page 125

Convertisseur de fréquence
Masquer les pouces Voir aussi pour Global Drive 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Show/Hide Bookmarks
Code
No.
Name
C0003*
Non-volatile
v
parameter saving
C0004*
Bar-graph display
C0005
Fixed configuration
v
analog input signals
C0007
Fixed configuration of
v
digital inputs
u u u u S S S S E E E E r r r r
L
Possible settings
Lenze
Selection
-1-
0
Parameter not saved in EEPROM
i
1
Parameter always saved in EEPROM
3
Own settings saved in EEPROM
56
1
56 = controller load (C0056)
-0-
0
Setpoint for speed control via X3/8 or X3/1U, X3/1I
1
Setpoint for speed control via X3/8 with setpoint
summation via frequency input X3/E1
2
Setpoint for speed control via frequency input X3/E1
with setpoint summation via X3/8
3
Setpoint for speed control via frequency input X3/E1,
torque limitation via X3/8 (power control)
4
Setpoint for sensorless torque control via X3/8, speed
limitation via C0011
5
Setpoint for sensorless torque control via X3/8, speed
limitation via frequency input X3/E1
6
Controlled operation; setpoint via X3/8 with digital
feedback via X3/E1
7
Controlled operation; setpoint via frequency input
X3/E1 with analog feedback via X3/8
200
All digital and analog input signals are sent via the
field bus function module (e. g. INTERBUS or
PROFIBUS-DP)
255
Free configuration under C0412
0
E4
0
CW/CCW
1
CW/CCW
2
CW/CCW
3
CW/CCW
4
CW/CCW
5
CW/CCW
6
CW/CCW
7
CW/CCW
8
CW/CCW
9
CW/CCW
10
CW/CCW
EDK82EV903 DE/EN/FR 1.0
Commissioning
{Code No.}
989
E3
E2
E1
DCB
JOG2/3
JOG1/3
PAR
JOG2/3
JOG1/3
QSP
JOG2/3
JOG1/3
PAR
DCB
JOG1/3
QSP
PAR
JOG1/3
DCB
TRIP set
JOG1/3
PAR
TRIP set
JOG1/3
PAR
DCB
TRIP set
QSP
PAR
TRIP set
QSP
TRIP set
JOG1/3
TRIP set
UP
DOWN
Code table
IMPORTANT
Data loss after mains disconnection
Active after every main connection
Cyclic parameter changes via bus module
are not allowed.
The parameter set 1 saved as own basic setting
with C0002 = -9-
Bargraph display indicates the selected in %
after power on
after power on
Range -180 % ... +180 %
Change under C0005 will be copied to the
corresponding subcode of C0412. Free
configuration under C0412 sets C0005 =
255!
Only active if C0014 = -5- (torque selection)
Sets C0410/x = 200 and C0412/x = 200
Only display
Do not change C0005 since settings under
C0412 can be lost
Change under C0007 will be copied to the
corresponding subcode of C0410. Free
configuration under C0410 sets C0007 =
255!
CW/CCW = CW rotation/CCW rotation
DCB = DC-injection brake
j
QSP = Quick stop
PAR = Parameter set changeover (PAR1 ó
PAR
P
t
t h
(PAR1 ó
PAR2)
PAR2)
– PAR1 = LOW PAR2 = HIGH
– PAR1 = LOW, PAR2 = HIGH
– The terminal must be assigned to the
– The terminal must be assigned to the
function "PAR" in PAR1 and PAR2.
– Configurations with "PAR" are only
allowed if C0988 = 0
allowed if C0988
0
TRIP set = external fault
TRIP set = external fault
47