Lenze Global Drive 8200 vector Instructions De Montage page 135

Convertisseur de fréquence
Masquer les pouces Voir aussi pour Global Drive 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Show/Hide Bookmarks
Code
No.
Name
C0142
Start condition
v
v
C0143*
Selection of
v
flying-restart
fl i
C0144
No temperature
v
v
depending chopper
p
frequency derating
f
C0145*
Process controller
v
setpoint source
i
C0148*
Motor parameter
s
identification
L
Possible settings
Lenze
Selection
1
0
Automatic start inhibited
Flying restart not active
1
Automatic start, if X3/28 = HIGH
Flying restart not active
2
Automatic start inhibited
Flying-restart circuit active
3
Automatic start, if X3/28 = HIGH
Flying-restart circuit active
0
0
Max. output frequency (C0011) ... 0 Hz
1
Last output frequency ... 0 Hz
2
Frequency setpoint addition (NSET1-NOUT)
3
Act. process controller value (C0412/5) addition
(PCTRL1-ACT)
1
0
No temperature-depending chopper frequency
g
pp
derating
d
ti
Automatic chopper frequency derating at ϑ
1
0
0
Total setpoint (PCTRL1-SET3)
1
C0181 (PCTRL1-SET2)
2
C0412/4 (PCTRL1-SET1)
0
0
Ready
1
Start identification
V/f-rated frequency (C0015), slip compensation
(C0021) and motor stator inductivity (C0092) are
calculated and saved.
The motor stator resistance (C0084) = total
resistance of motor cable and motor is measured
and saved
EDK82EV903 DE/EN/FR 1.0
Commissioning
Code table
IMPORTANT
Start after LOW-HIGH level change at X3/28
Start after LOW-HIGH level change at X3/28
Motor speed selected for the indicated range
p
The corresponding value is input after controller
p
g
enable.
bl
- 5 °C
max
Main setpoint + additional setpoint
Setpoint selection not possible via
– JOG values
j
function of the keypad
– C0044, C0046 and C0049
– in connection with manual/remote
in connection with manual/remote
changeover, skip frequencies, ramp
function generator, additional setpoint
Activate the automatic DC-injection brake
(auto DCB) with C0019 = 0 or C0106 = 0
Only when the motor is cold!
1. Inhibit controller, wait until drive is in
standstill
2 Enter the correct motor data under C0087
2. Enter the correct motor data under C0087,
C0088, C0089, C0090, C0091 (see motor
nameplate).
v
3. C0148 = set 1 by
4. Enable controller
The identification
c
– starts,
Off
– takes approx. 30 s
– is completed when
5. Controller inhibit
g
p
c
is on again
57

Publicité

Table des Matières
loading

Table des Matières