Code
No.
Name
C0161*
Actual fault
C0162*
Last fault
C0163*
Last but one fault
C0164*
Last but two fault
C0165
Service code
LECOM
C0168*
Actual fault
C0170
Configuration TRIP
v
v
reset
C0171
Delay for auto-TRIP
reset
C0174*
C0178*
Operating time
C0179*
Mains switch-on
time
C0181*
Process controller
setpoint 2
(PCTRL1-SET2)
C0182*
Integration time
S–ramps
C0183*
Diagnosis
g
C0184*
Frequency threshold
PCTRL1-I-OFF
C0185*
Switching window for
"frequency setpoint
reached (C0415/x =
4)" and
"NSET1-RFG1-I=O
(C0415/x = 5)"
C0189*
Output signal
compensator
(A)
CTRL1-FOLL1-OUT)
L
Possible settings
Lenze
Selection
0
0
TRIP reset by mains switching,
X3/28, via function module or communication module
1
like -0- and additional auto TRIP reset
2
TRIP reset through mains switching, via function
module or communication module
3
TRIP reset by mains switching
0.00
0.00
0.00
-650.00
0.00
0.00
0
No fault
102
TRIP active
104
Message "Overvoltage (
active
142
Pulse inhibit
151
Quick stop active
161
DC-injection brake active
250
Warning active
0.0
0.0
0
0
-650.00
EDK82EV903 DE/EN/FR 1.0
Commissioning
s
, LOW–signal at
{0.01 s}
60.00
{h}
{h}
{0.02 Hz}
650.00
{0.01 s}
50.00
O O O O U U U U
)" or "Undervoltage (
L L L L U U U U
)"
{0.1 Hz}
25.0
{1 %}
80
{0.02 Hz}
650.00 Only display
Code table
IMPORTANT
Display history buffer contents
p y
y
•
Keypad: three-digit, alpha numerical fault
detection
detection
•
•
9371BB keypad: LECOM fault number
9371BB keypad: LECOM fault number
Modifications only by Lenze Service!
Display history buffer contents
•
Keypad: three-digit, alpha numerical fault
detection
•
9371BB keypad: LECOM fault number
•
TRIP reset via function module or
communication module with C0043,
C0410/12
C0410/12 or C0135 bit 11.
C0135 bit 11
•
•
Auto TRIP reset after the time set under
Auto TRIP reset after the time set under
C0171.
not active
Only display
Total duration terminal 28 (CINH) = HIGH
Only display
Total time mains on
•
C0182 = 0.00: Linear ramp function
generator operation
•
C0182 > 0.00: S-shaped ramp function
generator (smooth)
Only display
y
p y
•
If the output frequency i < C0184, the I
component of the process controller will be
switched off
•
0.0 Hz = Function not active
•
C0415/x = 4 and C0415/x = 5 are active
within a window around NSET1-RFG1-IN
•
Window in C0185 = 0%:
± 0,5 % ref. to C0011
•
Window in C0185 > 0%:
± C0185 ref. to NSET1-RFG1-IN
Compensator = PCTRL1-FOLL1
,
59