Commissioning
Code table
Code
No.
Name
C0015
V/f rated frequency
u u u u S S S S E E E E r r r r
C0016
V
boost
min
u u u u S S S S E E E E r r r r
C0017
Frequency threshold
Q
min
C0018
Chopper frequency
pp
q
y
v
C0019
Operating threshold
for automatic
DC-injection brake
(Auto-DCB)
C0021
Slip compensation
C0022
I
limit (motor
max
mode)
C0023
I
-limit in the
max
generator mode
C0026*
Offset analog input 1
(AIN1–OFFSET)
C0027*
Gain analog input 1
(AIN1-GAIN)
C0034*
Setpoint selection
range
g
v
S
Standard–I/O (X3/8)
d d I/O (X3/8)
u u u u S S S S E E E E r r r r
C0034*
Setpoint selection
v
range
Application- I/O
(A)
u u u u S S S S E E E E r r r r
1 X3/1U, X3/1I
2 X3/2U, X3/2I
C0035*
DC injection brake
j
v
(DCB) control mode
(DCB)
l
d
50
Possible settings
Lenze
Selection
50.00
7.50
à
0.00
0.00
0.00
6
0
2 kHz sin
1
4 kHz sin
2
8 kHz sin
3
16 kHz sin
4
2 kHz f_top
5
4 kHz f_top
6
8 kHz f_top
7
16 kHz f_top
8
1 kHz sin
Reserved
9 ... 11
12
1 kHz f_top
0.10
0.00
= not active
0.0
-50.0
150
30
150
30
0.0
-200.0
100.0
-1500.0
0
0
0 ... 5 V / 0 ... 10 V / 0 ... 20 mA
1
4 ... 20 mA
2
-10 V ... +10 V
3
4 ... 20 mA Open-circuit monitoring
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
1
Voltage bipolar -10 V ... +10 V
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
4
Current 4 ... 20 mA open-circuit monitored
0
0
Brake voltage selection under C0036
1
Brake current selection under C0036
EDK82EV903 DE/EN/FR 1.0
{0.02 Hz}
960.00 Setting applies to all mains voltages permitted
{0.01 %}
40.00
{0.02 Hz}
650.00 Programmable frequency threshold
low noise generation
low noise generation
low power loss
low power loss
low power loss
650.00 Holding time ð C0106
{0.02 Hz}
{0.1 %}
50.0
{1 %}
150 After controller enable, 180% I
{1 %}
150 C0023 = 30 %: function is inactive, if
{0.1 %}
200.0
{0.1 %}
1500.0
IMPORTANT
Depending on the controller
à
Setting applies to all mains voltages permitted
Reference: Setpoint
Signal output configuration under C0415
General rule:
The lower the chopper frequency
th l
the lower the power loss
th
l
the higher the noise generation
the higher the noise generation
the better the smooth running quality
the better the smooth running quality
Medium-frequency motors are only allowed
Medium-frequency motors are only allowed
to be operated at 8 kHz sin or 16 kHz sin
to be operated at 8 kHz sin or 16 kHz sin
(C0018 = 2 or 3)!
(
)
Deactivate the automatic DC injection brake
when the minimum frequency limit C0239 is
active
are available for
r
max. 3 s at C0022 = 150 %
C0014 = 2, 3:
Settings for X3/8 and X3/1U, X3/1I
The max. limit of the setpoint value range of
C0034 equals 100 %
C0026 and C0413/1 are identical
Settings for X3/8 and X3/1U, X3/1I
100.0 % = Gain 1
Inverse setpoint selection by negative gain
and negative offset
C0027 and C0414/1 are identical
Observe the switch position of the function
module!
Minimum output frequency (C0010) not
effective
Individual adjustment of offset and gain
TRIP Sd5, if I < 4 mA
Observe the jumper setting of the function
module!
Minimum output frequency (C0010) not effective
TRIP Sd5 if I < 4 mA
Holding time ð C0107
g
L