8 3
SIGNALS ON THE CONTROL UNIT
The control unit has LEDs 'L1-L4' located on the keys ("Figure 53").
Each of these LEDs can emit specific signals, both during normal op-
eration and in the event of a fault. The cause and possible solution for
each type of fault are described in "Table 19 .
TERMINAL LEDS ON THE CONTROL UNIT
Status
ECSbus LED
OFF
On
1 flash per second, green
color
1 long flash of the green
LED
1 green flash every 5
seconds
Series of red flashes
separated by a 1-second
pause
Fast flashing of the red LED ECSbus short circuit
STOP LED
OFF
On
SbS LED
OFF
On
OPEN LED
OFF
On
L1 LED
OFF *
On
Series of fast flashes (from
1 to 4)
5 fast flashes
3 slow flashes
5 slow flashes
L2 LED
OFF *
On
1 flash per second
2 flashes per second
36 – ENGLISH
Meaning
Anomaly
Serious anomaly
Everything normal
The status of the inputs has
changed
Automation in standby mode
Various
Intervention of the STOP input Check the devices connected to the STOP input.
Everything normal
Everything normal
Intervention of the SbS input
Everything normal
Intervention of the OPEN input This is normal if the device connected to the OPEN input is actually active.
All OK
Storage in Mode 1
Storage in Mode 2
Deletion OK
Memory OK
Deletion OK
All OK
All OK
The learning phase has not
been performed or there are
errors in the data stored in
memory
Device learning phase in
progress
53
Possible solution
Check for the presence of power; check that the fuses are not blown; if necessary,
identify the cause of the fault then replace them with fuses having the same
specifications.
There is a serious anomaly; try switching off the control unit for a few seconds; if the
condition persists, it means that there is a fault and the electronic circuit board must
be replaced.
Normal control unit operation.
This is normal when there is a change in one of the inputs: SBS, STOP, OPEN,
CLOSE, the photocells intervene or the radio transmitter is used.
Everything is normal; when the control unit receives a command, it resumes normal
operation (after a short delay).
Refer to the information in 'Table 18'.
To activate the ECSbus power supply, simply give a command (e.g. with the
transmitter).
STOP input active.
SbS input not active.
This is normal if the device connected to the SbS input is actually active.
OPEN input not active.
No storage in progress.
This is normal during storage in Mode 1, which lasts for a maximum of 10 seconds.
This is normal during storage in Mode 2, which lasts for a maximum of 10 seconds.
Deletion of a transmitter successful.
Memory successful.
Deletion of all transmitters successful.
'Slow' speed selected.
'Fast' speed selected.
Perform the position learning phase again (see chapter Storing connected
devices).
Indicates that the search for connected devices is in progress (lasts a few seconds
at most).
Table 19