Wall-mounting procedure

The monitor can be mounted onto a wall by following this procedure� Monitors with
the optional temperature sensor must be mounted in a location with relatively still
air�
1� Center the mounting plate over the wires from the wall with the mounting holes�
2� With a pencil, mark the locations for the two mounting holes� Typical mounting
hole distances are shown in this illustration�
2 in.
(51 mm)
1-13/16 in.
(46 mm)
2-5/16 in.
(59 mm)
1-13/16 in.
(46 mm)
Figure 15. Various mounting distances of the nine backplate mounting holes
3� Drill a hole in the wall at each of the marks�
4� Insert a plastic anchor into each of the holes until they are flush with the wall�
5� Thread the wires through the back of the backplate� Refer to the wiring
illustrations on the following pages for various configurations�
6� Attach the backplate to the wall by screwing the supplied metal screws into the
plastic anchors� Torque installation screws to 11 in-oz (79 Nmm)�
7� Connect each of the wires to the corresponding terminals on the backplate, as
shown in the following illustration�
8� Set the slide switches according to the configuration of the monitor� (Slide the
switches up for milliamps or down for volts�)
9� Align the bottom of the bezel with the mounted assembly and rotate the top into
place� Press firmly until it snaps�
10� Torque the case hex screws to 7-10 oz-in (0�59-0�85 Nm)�
1 The monitor has an internal 500 ohm termination resistor. Default output is mA..
3-1/4 in.
(83 mm)
1
IAQPoint2™
17