Wall Mount Installation

Affix the SQN8x transmitter to the wall at a height of 5 ft. (1.5 meters)
from the floor. Affix all sensors at an appropriate height and location, as
shown in the table. Place the sensors in a perimeter around a heat sink,
a boiler or all other equipment that should be monitored.

Recommended Installation Height

The installation heights recommended by Honeywell represent general
guidelines. Always confirm local laws and regulations before
proceeding, as these take precedence over manufacturer's
recommendations.
Detected Gas
CO
Carbon monoxide
NO
Nitrogen dioxide
2
O
Oxygen
2
R11
R12
R22
Refrigerants
R123
R125
R134A
Most combustibles are heavier than air, with the exception of
methane, hydrogen,ethylene and acetylene. For gases that are
heavier than air, sensors should be installed approximately 30 cm
COMB
(1 ft.) from the floor. For combustibles that are lighter than air,
sensors should be installed 30 cm (1 ft.) from the ceiling, close to
the potential leak source.
* May differ for certain uses. For example, heated NO
exhaust system is lighter than 1.58.
512226
2/08
Relative
Density
(air = 1)
0.968
1.58
(cold)
1.43
5.04
4.20
3.11
5.27
4.14
3.52
SQN8X User Manual
Honeywell
Wall Mount Installation
Installation Height
3 - 5 ft. (1 - 1.5 m) from floor
*1 - 3 ft. (30 cm to 1 m) from
ceiling
3 - 5 ft. (1 - 1.5 m) from floor
1 ft. (30 cm) from floor