Wall-mount Installation

Installation of the monitor simply requires the physical mounting of the
enclosure and connection of the power and output lines.
Detected Gas
C
H
O
Ethylene oxide
2
4
CL
Chlorine
2
CO
Carbon monoxide
H
S
Hydrogen sulfide
2
H
Hydrogen
2
HCL
Hydrogen chloride
HCN
Hydrogen cyanide
NO
Nitrogen monoxide
NO
Nitrogen dioxide
2
O
Oxygen
2
SO
Sulfur dioxide
2
R11
R12
Refrigerants
R22
R134A
Most combustibles are heavier than air, with the exception of methane, hydro
gen,ethylene and acetylene. For gases that are heavier than air, sensors should
COMB
be installed approximately 30 cm (1 ft.) from the floor. For combustibles that are
lighter than air, sensors should be installed 30 cm (1 ft.) from the ceiling, close
to the potential leak source.
* May differ in certain applications. Hot NO 2 from exhaust systems is
lighter than ambient air.
Note: The installation heights recommended by Honeywell represent
general guidelines. Always confirm with local laws and
regulations before proceeding, as these take precedence over
manufacturer's recommendations.
511391
2/07
Relative
Density
(air = 1)
1.50
2.50
0.968
1.19
0.07
1.30
0.932
1.04
1.58 (*cold)
1.43
2.25
5.04
4.20
3.11
3.52
201T User Manual
Honeywell
Wall-mount Installation
Installation Height
1 ft. (30 cm) from floor
1 ft. (30 cm) from floor
3 - 5 ft. (1 - 1.5 m) from floor
1 ft. (30 cm) from floor
1 ft. (30 cm) from ceiling
1 ft. (30 cm) from floor
1 ft. (30 cm) from ceiling
1 ft. (30 cm) from floor
1 - 3 ft. (30 cm to 1 m) from ceiling
3 - 5 ft. (1 - 1.5 m) from floor
1 ft. (30 cm) from floor
1 ft. (30 cm) from floor
13