Wiring Diagrams
Connecting Main Sensor to Remote
Figure 6. Connecting Main Sensor to Remote
The OUT1 and OUT2 connectors on the remote sensor's terminal
are not used. DO NOT connect any wires to these locations.
Wire: Signal wiring should be done with #20-24 AWG shielded twisted
pair cable Belden 9841 or similar. Remote sensors should have no more
than 200 ft (61 m) of #22 AWG wire. Smaller gauge sizes are limited by
the same resistance limit.
Power wiring should be sized by local codes, but never less than #20
AWG. 120 VAC wiring should be #14 or #12 AWG.