Troubleshooting; Faults And Warning Messages - Honeywell IAQPoint2 Guide De Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Troubleshooting

Faults and warning messages

Faults are handled in different ways, depending on the configuration of the unit� 4-20 mA loops will
drop below 2�0 mA� The relay will de-energize�
Affected
Models
• •
• •
IAQPoint2 Troubleshooting Guide
Version
Symptom
All analog outputs
• •
produce 0 mA or
0 VDC
One or more
• •
analog outputs
are lower than
expected.
Diagnostic
Cause
Tests
Measure voltage
between terminals
T9 and T7 and
confirm that 20-30
VAC or 18-28VDC is
supplied.
External wiring
has an error.
(Non-display models
only) Confirm that
the LED on the right
side flashes for 5
seconds after power
is applied.
IAQPoint2 is
defective.
Confirm that
Internal 500 Ω
switches for volt/
load resistors
milliamp mode are
are improp-
in the desired posi-
erly switched in
tion as described in
circuit.
Figures 16 and 20.
Confirm continuity
External equiment
in the external loop
does not share a
with an ohmmeter.
common ground.
Confirm voltage
between terminals
T7 and each of T4,
External imped-
T5 and T6 is less
ance is too high.
than 10.0 VDC while
the monitor is con-
nected.
IAQPoint2™
Solution
Provide 24 V AC/DC
power.
Replace.
Slide switches to
the correct position
as described in
Figures 16 and 20.
Rearrange external
circuit to have loops
as shown in Figure
9 or 10.
Rearrange external
current loop to have
R<=500 Ω.