BACnet/IP MODULE
Object Examples
In the first example, we see the CO
Vulcain network device:
Name :
"301D2 CO2 AD:14.CO2"
Value :
600
Units :
PPM
Object :
1.AI2*
Description : Analog Input
* 1 is the 301C unique device instance, AI is the object type and 2 is the
unique instance of the object in this device. We identify this object as
"Analog Input 2 of BACnet device 1".
In this example, we can see the output status for relay 2 of the same
Vulcain network device, but with a different device display label:
Name :
"Floor 01 Sensor 02 .rel2"
Value :
OFF
Units :
Object :
1.BO4*
Description : Binary Output
*We identify this object as "Binary Output 4 of BACnet device 1".
Example 3 where we can see the first 24V output status of a 301EM
Vulcain network device.
Name :
"301EM CO AD:25.out1"
Value :
OFF
Units :
Object :
1.BV1
Description : Binary Value*
*We identify this object as "Binary Value 1 of BACnet device 1".
98
gas sensor input for a 301D
2
301C User Manual