5. Operation

5.1 General

The motors are designed for the following conditions unless
otherwise stated on the rating plate:
- Motors are to be installed in fixed installations only.
- Normal ambient temperature range is from -20 °C to
+40 °C.
- Maximum altitude is 1000 m above sea level.
- The variation of the supply voltage and frequency may
not exceed the limits mentioned in relevant standards.
Tolerance for supply voltage is ±5 %, and for frequency
±2 % according to the figure 4 (EN / IEC 60034-1,
paragraph 7.3, Zone A). Both extreme values are not
supposed to occur at the same time.
The motor can only be used in applications for which
it is intended. The rated nominal values and operation
conditions are shown on the motor rating plates. In
addition, all requirements of this manual and other related
instructions and standards must be followed.
If these limits are exceeded, motor data and construction
data must be checked. Please contact ABB for further
information.
WARNING!
Ignoring any instructions or maintenance of the
apparatus may jeopardize safety and thus prevent
the use of the motor.
10
ABB Motors and Generators | Low voltage motors manual, 3GZF500730-85 Rev F 02-2015
Standard_Manual_LV_Motors_ML_revF_Book.indb 10
6/2/2015 6:44:25 PM