Metering Monitoring / Stop Pump; Metering Monitoring / Strokes - Ecolab Elados EMP IV E60 Notice Technique

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

10.3.13.2 Metering monitoring / Stop pump

10.3.13.3 Metering monitoring / Strokes

10.3.13.4 Metering monitoring / Deviation (only at E60
A tolerance in % is set under "deviation".
The actual incoming pulse rate recorded by the oval gear meter within the pump interval to
be monitored (see chapter
pulse rate defined during calibration.
If this comparison results in a deviation that is greater than the % value configured under
"deviation", a "metering monitoring alarm" is triggered.
This function can only be selected if a dongle plate is connected and configuration/oval gear
NOTE
meter (see chapter 10.3.11) has been activated.
417101799_EMP_IV_E60.docx
10.3.13.3
configuration/strokes) is compared with the target
- 100 -
Fig. 10.35
The "stop pump" function is used
to set whether or not the pump
should be stopped if a "metering
monitoring alarm" is triggered.
- Pump is not stopped
when a "metering monitoring alarm"
is triggered. (Default setting)
 Pump is stopped
when a "metering monitoring alarm"
is triggered.
Fig. 10.36
The "strokes" option indicates the
stroke interval to be monitored.
Setting range: 0 – 100
Default setting = 10
PLUS
PLUS
& OGM or OGM
Fig. 10.37
Setting range: 0-100%
Default setting = 20 %
)
Rev. 9-06.11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Elados emp iv e60plus

Table des Matières